Fix live wiresheet config/runtime slot alignment and cap float display to 2 decimals
Slots with no flags (sensor, controlSignal, out_*) were not skipped
during config property reads, consuming bytes that the device never
sent and misaligning every subsequent config value (setpoint,
proportionalBand, etc.) into tiny denormalized floats like 2.36875e-41.
Changed the filter in _apply_props from "skip if runtime" to "skip if
not config" so only explicitly config-flagged slots are read from config
messages. Also switched iter("slot") to findall("slot") in the slot
registry builder to avoid picking up nested descendants.
Float display now defaults to 2 decimal places everywhere (wiresheet
and properties panel), honouring the precision facet when one exists.
Co-Authored-By: Claude Opus 4.6 <noreply@anthropic.com>
This commit is contained in:
@@ -831,9 +831,8 @@ class SoxClient:
|
||||
continue
|
||||
if operator_only and not slot.get("is_operator"):
|
||||
continue
|
||||
is_config = slot.get("is_config", True)
|
||||
is_runtime = slot.get("is_runtime", False)
|
||||
if what_char == 'c' and is_runtime:
|
||||
is_config = slot.get("is_config", False)
|
||||
if what_char == 'c' and not is_config:
|
||||
continue
|
||||
if what_char == 'r' and is_config:
|
||||
continue
|
||||
|
||||
Reference in New Issue