Fix live wiresheet config/runtime slot alignment and cap float display to 2 decimals
Slots with no flags (sensor, controlSignal, out_*) were not skipped
during config property reads, consuming bytes that the device never
sent and misaligning every subsequent config value (setpoint,
proportionalBand, etc.) into tiny denormalized floats like 2.36875e-41.
Changed the filter in _apply_props from "skip if runtime" to "skip if
not config" so only explicitly config-flagged slots are read from config
messages. Also switched iter("slot") to findall("slot") in the slot
registry builder to avoid picking up nested descendants.
Float display now defaults to 2 decimal places everywhere (wiresheet
and properties panel), honouring the precision facet when one exists.
Co-Authored-By: Claude Opus 4.6 <noreply@anthropic.com>
This commit is contained in:
+24
-10
@@ -13,12 +13,22 @@ import schema
|
||||
from sox import SoxClient, SoxComponent, TREE, CONFIG, RUNTIME, LINKS, ALL
|
||||
|
||||
|
||||
def _fmt_float(val):
|
||||
"""Format a 32-bit float for display: 6 significant digits, always with a decimal point."""
|
||||
s = f"{val:.6g}"
|
||||
if "." not in s and "e" not in s and "E" not in s:
|
||||
s += ".0"
|
||||
return s
|
||||
def _fmt_float(val, precision=2):
|
||||
"""Format a float for display with *precision* decimal places (default 2)."""
|
||||
return f"{val:.{precision}f}"
|
||||
|
||||
|
||||
def _slot_precision(type_name, slot_name):
|
||||
"""Looks up the precision facet for a slot, returning 2 as the default."""
|
||||
reg = app_state.final_components_registry.get(type_name)
|
||||
if reg:
|
||||
for s in reg:
|
||||
if s["name"] == slot_name:
|
||||
p = s.get("facets", {}).get("precision")
|
||||
if isinstance(p, int) and 0 <= p <= 12:
|
||||
return p
|
||||
break
|
||||
return 2
|
||||
|
||||
|
||||
class DeviceSession:
|
||||
@@ -100,7 +110,7 @@ class DeviceSession:
|
||||
for type_elem in manifest.iter("type"):
|
||||
if type_elem.get("name") == "Component":
|
||||
slots = []
|
||||
for slot_elem in type_elem.iter("slot"):
|
||||
for slot_elem in type_elem.findall("slot"):
|
||||
slot_name = slot_elem.get("name", "")
|
||||
slot_id = int(slot_elem.get("id", "-1"))
|
||||
slot_type = slot_elem.get("type", "int")
|
||||
@@ -127,7 +137,7 @@ class DeviceSession:
|
||||
if type_id_val < 0:
|
||||
continue
|
||||
slots = []
|
||||
for slot_elem in type_elem.iter("slot"):
|
||||
for slot_elem in type_elem.findall("slot"):
|
||||
slot_name = slot_elem.get("name", "")
|
||||
slot_id = int(slot_elem.get("id", "-1"))
|
||||
slot_type = slot_elem.get("type", "int")
|
||||
@@ -276,7 +286,7 @@ class DeviceSession:
|
||||
if name in sox_comp.values:
|
||||
val = sox_comp.values[name]
|
||||
if isinstance(val, float):
|
||||
val_str = _fmt_float(val)
|
||||
val_str = _fmt_float(val, _slot_precision(type_qname, name))
|
||||
else:
|
||||
val_str = str(val)
|
||||
ET.SubElement(comp_elem, "prop",
|
||||
@@ -364,6 +374,7 @@ class DeviceSession:
|
||||
if comp_elem is None:
|
||||
return None
|
||||
|
||||
type_name = sox_comp.type_name
|
||||
slots = self.sox_client.slot_registry.get(
|
||||
(sox_comp.kit_id, sox_comp.type_id))
|
||||
if slots:
|
||||
@@ -374,7 +385,10 @@ class DeviceSession:
|
||||
name = slot["name"]
|
||||
if name in sox_comp.values:
|
||||
raw = sox_comp.values[name]
|
||||
val = _fmt_float(raw) if isinstance(raw, float) else str(raw)
|
||||
if isinstance(raw, float):
|
||||
val = _fmt_float(raw, _slot_precision(type_name, name))
|
||||
else:
|
||||
val = str(raw)
|
||||
if name in existing_props:
|
||||
existing_props[name].set("val", val)
|
||||
else:
|
||||
|
||||
Reference in New Issue